Estimated Availability Date:
Call for price & availability : 403-287-5340
The Fluke T6-600 Electrical Tester is built with Fluke's integrated FieldSense technology, you can quickly and easily take measurements by sliding the open fork over a conductor to see the voltage level without the need for test leads.*
* Voltage measurement requires capacitive path to ground, provided through user in most applications. Ground connection via test lead may be required in some situations.
Build
Why use the T6 Electrical Tester?
- Electricians often work in boxes jammed with wires, where finding a safe metallic contact point can be a challenge. With the T6-600 or T6-1000 you take measurements by sliding a single wire into the open fork.
How FieldSense Works
- FieldSense technology is truly a breakthrough in how voltage is measured. While other open fork testers detect a magnetic field to show ac current, FieldSense technology detects an electrical field. This field interacts with a reference signal created by the T6 tester, creating a voltage value on the tester’s display.
Who needs a T6 tester?
- Commercial and light industrial electricians can use T6 Electrical Testers for most everyday measurements. These devices easily fit in your pocket, making them easy to access on the front-line for electricians of all industries.
Resistance 1 Ω to 2000 Ω
Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
Certifications & Safety
Safety | IEC/EN 61010-1: Pollution Degree 2 | |
---|---|---|
Electromagnetic Environment | IEC/EN 61326-1: Portable |
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding. Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground. Accuracy[3]: FieldSense is specified from 16 V to 100 % of range. | ||||
Function | Requires test leads | Range | Resolution | Accuracy[1] |
---|---|---|---|---|
FieldSense ac voltage true-rms | No | 600 V | 1 V | ±(3% + 3 counts) 45 Hz - 66 Hz[2] [3] |
FieldSense ac current true-rms | No | 200.0 A | 0.1 A | ±(3% + 3 counts) 45 Hz - 66 Hz |
FieldSense frequency (Hz) | No | 1 Hz | ±(1% + 2 counts)[3] | |
Volts ac true-rms | Yes | 600 V | 1 V | ±(1.5% + 2 counts) 45 Hz - 66 Hz |
Volts dc | Yes | 600 V | 1 V | ±(1% + 2 counts) |
Resistance | Yes | 2000 Ω | 1 Ω | ±(1% + 2 counts) |
Safety | 600 V CAT III |
Vendor Part #: | T6-600 |
Battery Life: | [360 Hours] continuous, typical; [200 Hours] using FieldSense |
Battery Requirements: | [2 AA] |
Depth: | [1.724409 inches] |
Height: | [10.208661 inches] |
Jaw Capacity: | [0.7007874 inch] |
Operating Temperature Range: | -10°C to 50°C |
Weight: | [0.78 lbs.] |
Width: | [2.405512 inches] |
Storage Temperature: | -30°C to 60°C |
Operating Humidity Range @ 30°C to 40°C: | 0% to 75% |
Operating Altitude: | [2000 m] |
Storage Altitude: | [10000 m] |
Operating Humidity Range @ 5°C to 30°C: | 0% to 90% |
Operating Humidity Range @ 40°C to 50°C: | 0% to 45% |
- Article | IP Ratings Learn more about what an IP rating is and how this rating system is used.